Description

The MZC-320s can make measurements of very low short circuit loop impedances (with resolution 0,1 mΩ) with a current of 130 A at 230 V; maximum 300 A at 550 V or with a current 24 A at 230 V, maximum 30 A at 550 V (with resolution 0,01 Ω)

  • Measurements in installations with rated voltages between: 110/190 V, 115/200 V, 127/220 V, 220/380 V, 230/400 V, 240/415 V i 290/500 V and frequencies 45…65 Hz.
  • The ability to perform measurements in short circuit system: phase-phase, phase-protective, phase-neutral.
  • Differentiation between the phase voltage and the inter-phase voltage while calculating the short circuit current.
  • The ability to change the length of test lead.
  • Four-pole method, test leads do not require calibration (measurement with current 300 A).
  • Touch voltage and touch shock voltage measurement with resistor 1 kΩ).
  • AC voltage measurement in range 0…550V.
  • Memory of 999 measurement results with an ability to transfer the data to a PC.
  • Download data with USB.
  • Meter meets the requirements of the standard EN 61557.

Download Datasheet MZC-320S