Sonel MRU-12

The Sonel MRU-12 earth resistance and soil resistivity meter is a simple meter that allows you to measure grounding by using the technical method (3-pole and 4-wire) and soil resistivity by Wenner and Schlumberger method. The earth tester is easy to use, resistive to interference, and highly accurate.

MRU-12 is a basic device that allows for checking the quality of the grounding system on the basis of the received measurement result. Its ergonomic shape, durable and firm housing, as well as big and clear display make this instrument ideal to use both in the field and most working environments.

Contact us to inquire about this product

If you are interested in this product and would like a quote please fill in the inquiry form on this page, and we will be happy to provide you with more info!

Description

The Sonel MRU-12 is the easy way to measure earthing and soil.

The Sonel MRU-12 earth resistance and soil resistivity meter is a simple meter that allows you to measure grounding by using the technical method (3-pole and 4-wire) and soil resistivity by Wenner and Schlumberger method. The earth tester is easy to use, resistive to interference, and highly accurate.

MRU-12 is a basic device that allows for checking the quality of the grounding system on the basis of the received measurement result. Its ergonomic shape, durable and firm housing, as well as big and clear display make this instrument ideal to use both in the field and most working environments.

The device is simple to operate and intuitive. It is the best choice for electrical installations contractors, technicians, and professionals dealing with grounding measurements.

Measurement methods

  • 3-pole and 4-wire method – measurement of earthing systems using auxiliary probes
  • 2-pole method
  • Earth resistivity
    • Wenner method
    • Schlumberger method

Additional features

  • Resistance of auxiliary electrodes RH and RS
  • Measurement of interference voltage to 100 V
  • Indication of battery state
  • Selection of maximum measuring voltage (25 V and 50 V)
  • Auto-OFF function
  • In ground resistivity measurements, distances between electrodes can be input in meters (m) or feet (ft)
  • Memory of 990 measurement results (10 banks of 99 cells each)

For more information visit the Sonel product page

Technical Specification

Measurement functions Measurement range Display range Resolution Accuracy
Interference voltage 0 V…100 V 0 V…100 V 1 V ±(10% m.v. + 1 digit)
Earth resistance
2-pole method 0.00…9999 Ω 0.00…9999 Ω from 0 0.01 Ω from ±(3% m.v. + 3 digits)
3-pole and 4-wire method 0.53…9999 Ω acc. to EN 61557-5 0.00…9999 Ω from 0 0.01 Ω from ±(3% m.v. + 3 digits)
auxiliary electrodes resistance 0 Ω…19.9 kΩ 0 Ω…19.9 kΩ from 0 1 Ω ±(5% + 8 digits)
Earth resistivity
Wenner method 0.0 Ωm…999 kΩm 0.0 Ωm…999 kΩm from 0.1 Ωm Depends on the accuracy of the RE 4p measurement, but not less than ±1 digit
Schlumberger method 0.0 Ωm…999 kΩm 0.0 Ωm…999 kΩm from 0.1 Ωm Depends on the accuracy of the RE 4p measurement, but not less than ±1 digit

“m.v.” – measured value

Downloadable Files

Sonel MRU-12 Datasheet

Title