Elspec G4610

Elspec G4610

The G4610 is more than a power quality analyser. With trigger-free continuous waveform recording, it captures the complete picture of your electrical network. As renewables, BESS, data centers, UPS systems, drives, and other power-electronic loads transform electrical networks, power quality issues are becoming more complex. The G4610 continuously captures and records even the short, intermittent, and oscillatory events so you can predict, prevent and troubleshoot easily and with confidence.

Contact us to inquire about this product

If you are interested in this product and would like a quote please fill in the inquiry form on this page, and we will be happy to provide you with more info!

Description

Elspec G4610 Power Quality and Grid Stability Analyser

The Full Electrical Story – Not Only the Events You Predicted

The G4610 is more than a power quality analyser. With trigger-free continuous waveform recording, it captures the complete picture of your electrical network. As renewables, BESS, data centers, UPS systems, drives, and other power-electronic loads transform electrical networks, power quality issues are becoming more complex. The G4610 continuously captures and records even the short, intermittent, and oscillatory events so you can predict, prevent and troubleshoot easily and with confidence.

Continuous waveform recording

  • The full waveform is recorded and stored without gaps
  • Over 5000 power parameters
  • @1/2 cycle resolution
  • PQZIP compression

Advanced oscillation detection

  • Detects, classifies and quantifies oscillatory behavior from inverter-based systems.

IEC 61000-4-30 Class A

  • Certified for the highest accuracy class for power quality measurement.

IEC 61850 / PMU / DNP3 / Modbus

  • A measurement node built for substation
  • SCADA and grid automation networks

Synchronized Monitoring

  • Aligns logged data from multiple units on a single time scale
  • Any grid event can be traced precisely to its source.

One Platform. Multiple Power-System Roles

  • Power Quality Monitoring
  • Digital Fault Recording
  • Synchrophasor / PMU
  • Sequence-of-Events Recording
  • Dynamic System Monitoring
  • Energy & Billing Measurement

PQZIP Continuous Waveform Recording

The G4600 redefines what a power quality analyzer can do. Powered by PQZIP technology, it enables long-term, high-resolution waveform recording and storage without relying on preconfigured triggers. Engineers can investigate not only the event that crossed a threshold, but also the conditions leading up to it, the system’s recovery behavior, and related disturbances across the network for a more complete understanding of power quality performance.

  • Threshold-free setup so there is to need for predefined the setup
  • High-resolution waveform supports up to 1024 samples/cycle
  • Synchronized measurement engine for simultaneous multi-channel sampling
  • Up to the 511th Harmonic for wide-band Harmonics spectral visibility
  • Precise ½ cycle frequency recording for fast frequency excursions, recovery behavior, generator start ups, UPS transitions, BESS response and grid-stability

Power quality analyzer with continuous waveform recording illustration to Detect, Quantify and Preserve The Evidence

Oscillation Detection for IBR-Dominant Systems

As renewable generation, BESS, UPS systems, power-electronic loads, FACTS/HVDC assets and weak-grid conditions increase, engineers need more than sag/swell logs. They need a power quality analyzer that can detect oscillatory behavior, quantify it, and connect it to the underlying waveform evidence.

Oscillation detection in Elspec’s G4600 power quality analyzer

  • Detection range
    • 0.05–55Hz oscillation detection for low-frequency and subsynchronous phenomena
  • Severity states
    • Real-time Event / Alarm / Trip classification with a clear severity hierarchy
  • System integration
    • Oscillation state and metrics available through supported protocols and PQZ data workflows
  • Selectable parameters
    • Operates on half-cycle or one-cycle parameters – frequency, RMS voltage/current, sequence components and power
  • Calculated metrics
    • Oscillation frequency, damping ratio, phase, maximum amplitude and average amplitude
  • Operational response
    • Use oscillation state to support alarms, digital outputs, relay outputs and Sapphire investigation.

Why it matters

Oscillations may stay within normal voltage or current limits while still indicating control-loop interaction, resonance, insufficient damping or developing instability.  Continuous waveform recording gives engineers the evidence to validate models, replay behavior and perform deeper EMT or power-system studies after the event.

Communication, I/O & Cyber Security – Connectivity & Communications

A measurement node within the digital electrical infrastructure, not just a standalone power quality analyzer. Supports standard utility and industrial protocols for SCADA, protection, automation, and power quality systems. Efficient low-bandwidth communication enables reliable data transfer from remote sites, while seamless integration ensures secure and time-synchronized data exchange across modern networks.

Continuous waveform recording

  • The full waveform recorded and stored without gaps
  • Over 5000 power parameters
  • @1/2 cycle resolution
  • PQZIP compression.

Advanced oscillation detection

  • Detects, classifies and quantifies oscillatory behavior from inverter-based systems.

IEC 61850 / PMU / DNP3 / Modbus

  • A measurement node built for substation
  • SCADA and grid automation networks.

Synchronized Monitoring

  • Aligns logged data from multiple units on a single time scale, so any grid event can be traced precisely to its source.

Multi I/O Modules

  • 24 Digital inputs
  • 12 Digital outputs
  • 12 Analog inputs
  • 12 Analog outputs
  • 9 Relay outputs

Where the G4600 Delivers

As renewable generation, BESS, UPS systems, power-electronic loads, FACTS/HVDC assets and weak-grid conditions increase, engineers need more than sag/swell logs. They need to detect oscillatory behavior, quantify it, and connect it to the underlying waveform evidence.

  • Power Quality Monitoring for Data Centers & Critical Loads
    • Data Centers & Critical Loads
    • Captures UPS transfers & generator starts
    • Switching events with full waveform context
    • Protects uptime through pre-event visibility
  • Utilities & Substations monitoring solutions
    • Utilities & Substations
    • IEC 61850 integration & PMU streaming
    • Disturbance investigation from a single device
    • Oscillation events time stamped with GPS/PTP accuracy
  • Inverter-Based Generation & BESS monitoring solutions
    • Inverter-Based Generation & BESS
    • Inverter switching behavior and control-loop interaction
    • Weak-grid dynamics
    • Grid-code compliance recorded automatically
  • Improving Industrial Plants power
    • Industrial Plants
    • Investigate production disruptions after the fact
    • No trigger threshold needed
    • Motor-drive harmonics, resonance andintermittent faults preserved
  • R&D and Testing computer labs power quality solutions
    • R&D and Testing
    • Continuous high-resolution
    • Electrical behavior capture
    • Model validation & comparison
    • Advanced analysis workflows

G4600 power quality analyzer features

Local & Central Interfaces

  • G4600 power quality analyzer smart display
  • A rugged 7″ touchscreen that automatically discovers one or multiple G4600 devices – RMS, power, energy, harmonics, phasors, waveforms, events and I/O status on site.
  • Powered and connected over a single PoE cable. Multitouch, operable with work gloves, indoor or outdoor. Also handles meter configuration and firmware updates.

Elspec PQ SCADA Monitoring Software

  • Real-time – live visibility
  • RMS, power, harmonics, unbalance, flicker, phasors, waveform, energy and I/O views.
  • Events – investigation
  • PQ, system, custom, aggregated and I/O events with threshold, rate-of-change and T-time comparison, logic aggregation, duration, phase, severity and value

Reports – export anywhere

  • EN50160, IEEE1159, grid-line-code reports, COMTRADE, PQDIF, PQZIP, Excel, CSV, PDF and image exports
  • Fleet – multi-site analysis
  • Centralized engineering software across many meters, sites and applications.

Technical Specification

Specifications

Voltage, current & frequency

Parameter

Measurement range

Resolution

Accuracy

VRMS (AC/DC) 0-1,000V¹ 10mV ±0.1% of nominal voltage
ARMS 0.01-79A 10mA ±0.1% of nominal current
Voltage peak up to 8kV 10mV ±0.1% of reading
Frequency (50Hz nom.) 40-70Hz 1mHz ±1mHz
Frequency (60Hz nom.) 40-70Hz 1mHz ±1mHz
¹ with a footnote that accuracy applies from 5V. ±0.1% of nominal voltage accuracy for nominal voltage 110 to 690V.

Harmonics, flicker & unbalance

Parameter

Measurement range

Resolution

Accuracy

Harmonic order 1 to 511 (subgroups per IEC 61000-4-7) 0.01V IEC 61000-4-7
Inter-harmonic order 1 to 511 (subgroups per IEC 61000-4-7) 0.01V IEC 61000-4-7
THD (n = 50) 0-1000% 0.01% ±0.25%
Phase angle -180° to +180° 0.01° ±0.01°
Flicker (Pst, Plt) 0-20 0.01 ±5%
Flicker (Pst inst.) 0-20 0.01 ±8%
Voltage unbalance (neg./zero seq.) 0-100% 0.1% 0.15%
Current unbalance (neg./zero seq.) 0-100% 0.1% 0.5%

Power & energy

Parameter

Measurement range

Resolution

Accuracy

Active power ±5kW × CT × PT ratio 10mW ±0.2%
Reactive power ±5kVAr × CT × PT ratio 10mVAr ±0.5%
Apparent power ±5kVA × CT × PT ratio 10mVA ±0.2%
Active energy ±5kWh × CT × PT ratio 10mWh ±0.1%
Reactive energy ±5kVArh × CT × PT ratio 10mVArh ±0.5%
Apparent energy ±5kVAh × CT × PT ratio 10mVAh ±0.2%

Inputs & sampling

Parameter

G4610

G4620

G4630

Voltage channels AC/DC: 4 AC/DC: 4 AC/DC: 4
Voltage range (direct) 1,000 VAC/VDC 1,000 VAC/VDC 1,000 VAC/VDC
Input impedance / capacitance 600V CAT IV / 1000V CAT III 600V CAT IV / 1000V CAT III 600V CAT IV / 1000V CAT III
Current channels 4 4 4
Current range 0.01-79A 0.01-79A 0.01-79A
Current burden 0.008VA @5A 0.008VA @5A 0.008VA @5A
Bandwidth 6.25kHz 12.5kHz 25kHz
Sampling rate 256 samples/cycle 512 samples/cycle 1024 samples/cycle
A/D converter 24-bit 24-bit 24-bit
Harmonics reach (50Hz) up to H128 up to H256 up to H511

PQZIP recording

Parameter

G4610

G4620

G4630

Continuous waveform ~1 week ~1 month ~1 year
Method Gap-less continuous recording of all electrical parameters – no event thresholds required Gap-less continuous recording of all electrical parameters – no event thresholds required Gap-less continuous recording of all electrical parameters – no event thresholds required
Event log memory up to 100000 event logs up to 100000 event logs up to 100000 event logs
Internal memory 64GB 64GB 64GB

Communication, time sync & power

Parameter

Specifications

Ethernet 2 × RJ45, 10/100/1000Mbit
LAN protocols Modbus TCP, DNP3, SSH, FTP, SFTP, PMU (IEEE C37.118), IEC 61850 (MMS/GOOSE/SV), PTP
Serial RS-485 / 422, Modbus RTU, up to 115,200 baud, full duplex
Power over Ethernet PoE-PSE output – 13W, 48VDC
Time synchronization GPS / NTP / IRIG-B / PTP / PPS / Self
Sync accuracy 0.5µs GPS & IRIG-B · 1µs PTP (Layer 2) · 100µs SNTP
Real-time clock ±5ppm
Power supply 85-264VAC, 47-63Hz · 120-370VDC · aux. 24VDC±20%
Low-voltage ride-through up to 30 seconds

Physical & environmental

Parameter

Specifications

Dimensions 174.6 × 231.7 × 183.2 mm (6.87″ × 9.12″ × 7.21″)
Weight 1.66 kg base (3.66 lb)/ 2.03 kg (1 MIO) (4.48 lb) / 2.38 kg (2 MIO) (5.25 lb)
Mounting DIN rail, enclosure or flat-surface
Ingress protection IP 20 per IEC 60529
Operating / storage temp -20 to +70°C / -40 to +85°C
Humidity / altitude 85% / up to 2,000m
Multi-I/O expansion up to 3 modules: 24 DI, 12 DO, 12 AI, 12 AO, 9 relays

Standard compliance

Standards IEC 61000-4-30 Class A, IEC 61000-4-7, IEC 61000-4-15, IEC 61000-4-19, IEEE 519, IEEE 1159, IEEE C37.118, IEC 62053-22/23/24, IEC 61850, EN 50160, IEC 62052-11/31, IEC 60068-2-1/2/6/14/27/57/78, IEC 60255-21-1/2/3, IEC 62262, IEC 60068-2-31, IEC 61010-1 safety, CISPR 32/FCC/ICES EMC, IEC 62586-1/2

Downloadable Files

Elspec G4610 Datasheet

Elspec G4610 Brochure

Go to Top