The Sonel WME-9 Comprehensive Test Kit for measurement of electrical installations is a set of measuring instruments with accessories that includes the Sonel MPI-502F multifunctional electrical installations meter, Sonel MIC-10 insulation resistance meter and Sonel CMP-200F fork clamp meter.
Sonel WME-9
Description
Sonel WME-9 Comprehensive Test Kit for measurement of electrical installations
A set of measuring instruments with accessories that includes:
- Sonel MPI-502F multifunctional electrical installations meter,
- Sonel MIC-10 insulation resistance meter,
- Sonel CMP-200F fork clamp meter.
Capabilities
- MPI-502F: Measurement of short circuit loop parameters.
- MPI-502F: Testing RCD breakers of AC, A types.
- MPI-502F and MIC-10: Measurement of resistance of protective conductors and equipotential bondings.
- MIC-10: Insulation resistance measurements with voltage up to 1000 V.
- CMP-200F: Measurement of voltage, current, resistance, capacitance.
Sonel MPI-502F multifunctional electrical installations meter
Measurement of short circuit loop parameters
- Measurement of short circuit loop impedance in networks with rated voltage: 220/380 V, 230 V/400 V, 240/415 V and frequency 45…65 Hz, operating voltage range: 180…460 V
- Indication of short circuit loop resistance R and short circuit loop reactance X
- Measurements of short circuit loop impedance with 15 mA current, without tripping the RCD circuit breaker
- Maximum test current: 7.6 A (at 230 V), 13.3 A (at 400 V)
- Testing RCD breakers of AC, A types
- Testing of prompt, short-delay and selective RCDs with rated current values 10, 15, 30, 100, 300, 500 mA
- Measurement of IA trip current and tripping time tA for currents 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
- RE and UB measurement without RCD tripping
- Extended AUTO function of RCD measurement, with the possibility of measuring ZL-PE with low current
- Measurement of IA and tA during one RCD tripping
- Measurement of resistance of protective conductors and equipotential bondings
- Measurement of protective connections continuity with a ±200 mA current in accordance with EN 61557-4
- Autocalibration of test leads – any leads can be used
- Low current resistance measurement with sound signaling
Sonel MIC-10 insulation resistance meter
Measurement of insulation resistance:
- Measurement voltage within the range of 50…1000 V: selected from 50, 100, 250, 500, 1000 V.
- Continuous reading of measured insulation resistance.
- Automatic discharge of the measured object’s capacitance upon completion of insulation resistance measurement.
- Sound signaling of five-second time intervals, facilitating capture of time characteristics.
- Readings of actual measurement voltage during measurement.
- Measurement current 1 mA.
- Protection against measurement of live objects.
Measurement functions:
- Insulation resistance measurement two- or three-lead method
- capacitance measurement during measurement of RISO
- Low-voltage measurement of continuity using current of ≥200 mA (RCONT)
- Low-voltage measurement of resistance (RX).
Additional functions of the meter:
- Measurement of direct and alternating voltages within the range of 0…600 V.
- Backlit keyboard and display.
- The instrument meets the requirements laid down by standard EN 61557.
Sonel CMP-200F fork clamp meter
Features:
- Fork-style clamp.
- AC current and AC voltage measurement.
- DC voltage measurement.
- Low-impedance voltage measurement – Low Z.
- Current measurement up to 200 A AC.
- Automatic selection of measuring ranges.
- HOLD function, allowing for freezing the result on the display.
- Function MAX/MIN for displaying extreme values.
- Auto-OFF function.
Technical Specification
Technical data
| MPI-502F | MIC-10 | CMP-200F | |
|---|---|---|---|
| Safety and work conditions | |||
| Measuring category according to EN 61010 | IV 300 V, III 600 V | IV 600 V, III 1000 V | IV 600 V, III 1000 V |
| Ingress protection | IP67 | IP67 | IP40 |
| Dimensions | 220 x 102 x 61 mm | 220 x 102 x 61 mm | 230 x 44 x 66 mm |
| Weight | ca. 0.8 kg | ca. 0.6 kg | ca. 0.3 kg |
| Memory and communication | |||
| Memory of measurement results | 990 cells, 10 000 records | – | – |
| Data transmission | Bluetooth | – | – |