Portable power quality analyser prepared for measuring in all types of networks in any kind of environments including outdoors.
Sonel PQM-700
Interested in this product? Send us a message for pricing or more information
Description
Analyser measures and records according to the IEC 61000-4-30 CLASS S STANDARD.
Features:
- Power to the analyser is supplied from tested mains (internal power supply) and is used in all types of networks from 64 V to 760 V, with particular emphasis on measurements at low voltage poles, due to the ease of connection,
- Has an independent power supply socket, especially suited for voltage measurements for transformers and DC circuits,
- Built-in real-time clock.
Possible measurements:
- Measurements according to EN 50160,
- Voltage L1, L2, L3,
– average, minimum, maximum and instantaneous values, range to 760 V, ability to work with voltage transformers, - Current L1, L2, L3, N (four inputs),
– average, minimum, maximum and instantaneous values, measurement current with range to 3 kA (depends on used clamp), ability to work with current transformers, - Crest factor for voltage and current,
- Frequency from 40 Hz to 70 Hz ,
- Active, reactive, distortion, apparent power, including the type of reactive power (capacitive, inductive),
- Power recording:
– Budeanu method,
– IEEE 1459, - Active, reactive, apparent energy,
- Power factor, cosφ, tgφ,
- Up to 40th harmonics for voltage and current,
- Total Harmonic Distortion (THD) for voltage and current,
- Short-term (PST) and long-term (PLT) flicker,
- Unbalance of voltage and current,
- Current and voltage events registration including waveforms and RMS graphs half period.
The Sonel PQM-700 is an approved product on the Energy Technology List.
Technical Specification
Parameters
Parameter | Measuring range | Max. resolution | Accuracy | |
---|---|---|---|---|
Alternating voltage (TRMS) | – | 0.0…760.0 V | 4 significant digits | ±0.5% Unom |
Crest Factor | Voltage | 1.00…10.00 (≤1.65 for 690 V voltage | 0.01 | ±5% |
Crest Factor | Current | 1.00…10.00 (≤3.6 dla Inom) | 0.01 | ±5% |
Alternating current (TRMS) | – | depending on clamp* | 4 significant digits | ±0.2% Inom (error does not account for clamp error) |
Frequency | – | 40.00…70.00 Hz | 0.01 Hz | ±0.05 Hz |
Active, reactive, apparent and distortion power | – | depending on configuration (transducers, clamps) | 4 significant digits | depending on configuration (transducers, clamps) |
Active, reactive and apparent energy | – | depending on configuration (transducers, clamps) | 4 significant digits | as power error |
cosφ and power factor (PF) | – | 0.00…1.00 | 0.01 | ±0.03 |
tgφ | – | 0,00…10,00 | 0.01 | depends on error of active and reactive power |
Harmonics | Voltage | DC, 1…40 | as for alternating voltage True RMS | ±0,15% Unom for m.v. < 3% Unom ±5% m.v. for m.v. ≥ 3% Unom |
Harmonics | Current | DC, 1…40 | as for alternating current True RMS | ±0.5% Inom for m.v. < 10% Inom ±5% m.v. for m.v. ≥ 10% Inom |
THD | Voltage and current | 0.0..100.0% (relative to RMS value) | 0.1% | ±5% |
Flicker index | – | 0.40…10.00 | 0.01 | ±10% |
Unbalance factor | Voltage and current | 0.0…10.0% | 0.1% | ±0.3% (absolute error) |
m.v. – measured value
*
- F-1A1, F-2A1, F-3A1 clamp: 0…1500 A AC (5000 Ap-p)
- F-1A, F-2A, F-3A clamp: 0…3000 A AC (10 000 Ap-p)
- F-1A6, F-2A6, F-3A6 clamp: 0…6000 A AC (20 000 Ap-p)
- C-4A clamp: 0…1000 A AC (3600 Ap-p)
- C-5A clamp: 0…1000 A AC/DC (3600 Ap-p)
- C-6A clamp: 0..10 A AC (36 Ap-p)
- C-7A clamp: 0…100 A AC (360 Ap-p)